TSB190225-021920
Service Bulletin Details
Public Details for: TSB190225-021920
This technical service bulletin describes the verification and resolution to an issue that arises when a C100D2re generator set is attempted to parallel with a c150, c200 or c275 generator set. When this occurs the b+ on the two units shor
- 9999 -
Models from 9999
9999 CUMMINS C |
2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Technical Service Bulletin Technical Service Bulletin: TSB190225 Released Date: 19-Feb-2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Warranty Statement The information in this document authorizes specific changes to the repair practice for failures covered under product warranty coverages. Contents Product Affected C100D2RE Issue When a C100D2RE generator set is attempted to parallel with a C150, C200 or C275 generator set, the B+ (24 VDC) on the two units short with each other, as a result of which the units cannot be paralleled, and temperature of the paralleling cable rises. Root Cause: Due to a design error in C100D2RE generator set harness, paralleling C100 with any other models causes the B+ (24 VDC) from one unit to be shorted to B+ on the other unit Verification/Confirmation Confirm if the unit has this issue by checking in the list of affected generator set serial numbers. See Table 2. Resolution On the harness of C100D2RE (PN: A054R546) shown in Figure 1 below: 1. Swap P70-A and P70-B 2. Swap J40-1 and J40-2 Service Instructions Follow all the necessary safety procedures along with Lock Out Tag Out. On the harness of C100D2RE (PN: A054R546) shown in Figure 1 below: https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 1/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue 1. Swap P70-A and P70-B 2. Swap J40-1 and J40-2 The harness is in the front panel inside the top rack of generator set. To locate connectors P70 and J40 with respect to the harness, refer to Figure 2. Figure 1, Harness A054R546 with P70 and J40 highlighted https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 2/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Figure 2, Location of connectors P70 and J40 on harness 1. Swapping connections of P70 connector (PN: 0323-1637) requires a Terminal Remover tool (refer to Figure 4 for examples) to remove the wires and reconnect them in the right location. Unplug the side clip on P70 connector as shown in Figure 3, before inserting the tool to remove wire connectors. https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 3/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Figure 3, P70 Connector Figure 4, Terminal Remover Tools https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 4/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue 2. J40 connector is a Deutsch connector (PN: 0323-2334) and the wires (size: 16 AWG) can be removed by removing the wedge (PN: 0323-2333) with a picker (refer to figure 5) and repositioning the wires in the right location. Figure 5, Picker to Remove Wedge Confirm the fix performed above by checking for continuity on the terminals between harnesses A054R544 (Figure 6) and A054R546 (Figure 1) indicated in Table 1, by using a multimeter. Note : The reworked connectors should be plugged back and battery switch should be in the OFF position to check for continuity. Table 1, Terminals and resistance values to be checked for continuity on harnesses A054R544 and A054R546 S. No. Terminals Resistance value required to indicate continuity 1 From J66A-12 to K23A-1 0 -1 ohm 2 From J66A-13 to K23A-2 0 -1 ohm 3 From TB3-5 to K20A-2 0 -1 ohm 4 From TB3-11 to K20-14 10k ohm https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 5/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Figure 6, Harness A054R544 showing location of connectors J66A and TB3 After the resolution is applied, put a green dot on J40 and P70 connectors as well as on the master label for A054R546 with a permanent marker. If the fix is done in-house, add an extra green dot on the shipping box. This will help identify repaired units and avoid misconnecting in future. Campaign details: Authorization number: 4035 Account code: 6 Travel: One trip allowed SRTs: 00-902 – administrative time – 0.7 99-999 – Install parallel wire ins – 0.3 Fail code: PR-WH-MR Expiration date: December 12, 2021 Table 2, List of Affected Serial Numbers A180287414 A180288358 A180300973 A180300973 A180307780 A180307781 A180307781 A180311216 A180311217 A180313643 A180313644 A180313644 A180316108 A180316108 A190470269 A190470271 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 6/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Table 2, List of Affected Serial Numbers A190472904 A190472942 A190473300 A190474502 A190474503 A190474520 A190474940 A190474980 A190479021 A190483031 A190486483 A190486485 A190488255 A190488256 A190488274 A190488772 A190488831 A190489344 A190489345 A190489351 A190489352 A190489353 A190490695 A190493435 A190500492 B180316609 B180316645 B180318731 B180318732 B190501278 B190501279 B190502108 B190502233 B190506462 B190507252 B190507453 B190507472 B190508153 B190508286 B190509731 B190512632 B190512651 B190515225 B190515678 B190515698 B190516157 C180332369 C180336449 C180336449 C180339323 C180339323 C180341659 C180341907 C180342405 C180345016 C180345225 C180345225 C180345664 C190518791 C190518812 C190519115 C190519131 C190519132 C190519831 C190519861 C190530071 C190530791 C190531987 C190532273 C190532311 C190533114 C190536207 C190536272 C190536291 C190537174 C190537959 C190537960 C190538325 C190538415 D180348999 D180350622 D180350622 D180350927 D180350927 D180351229 D180351229 D180351653 D180351653 D180352859 D180352859 D180353590 D180353591 D180353591 D180353593 D180353835 D180353953 D180353953 D180353955 D180353955 D180353955 D180354191 D180354305 D180354305 D180354711 D180354712 D190540193 D190540194 D190540194 D190540751 D190541688 D190542310 D190542314 D190545552 D190545553 D190547128 D190547458 D190548292 D190548311 D190549113 D190549131 D190549340 D190549371 D190549372 D190552810 D190552812 D190552831 D190553160 D190553161 D190553295 D190554332 D190554436 D190554473 D190554637 D190557749 D190557752 D190558064 D190559580 D190559631 E180357326 E180357721 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 7/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Table 2, List of Affected Serial Numbers E180357885 E180360471 E180360471 E180360473 E180360474 E180360719 E180360720 E180360720 E180361193 E180361193 E180361194 E180361195 E180361195 E180361234 E180363667 E180363668 E180363905 E180364314 E180364315 E180368942 E180368942 E180368943 E180368943 E180369729 E190559736 E190560539 E190560720 E190562176 E190562213 E190562214 E190562231 E190562357 E190562567 E190562807 E190562873 E190564244 E190564245 E190564852 E190564853 E190564854 E190564856 E190564857 E190565145 E190565732 E190566314 E190569452 E190569512 E190569513 E190570233 E190571005 E190571031 E190571571 E190571572 E190571591 E190571611 E190573672 E190573673 E190573692 E190573711 E190574359 E190574360 E190575200 E190575201 E190575202 E190577352 E190580052 F180369121 F180372734 F180373572 F180373572 F180373573 F180374057 F180375675 F180375676 F180375677 F180377908 F180377908 F180378495 F180378998 F180380302 F180386546 F180386547 F180386989 F180386990 F180387335 F180387336 F180387346 F190580017 F190580034 F190580776 F190580779 F190580780 F190581343 F190581343 F190581344 F190581345 F190584252 F190584253 F190584254 F190584603 F190584604 F190584605 F190584606 F190584955 F190585347 F190585348 F190585365 F190585606 F190587945 F190587946 F190587947 F190588722 F190588723 F190588731 F190588732 F190588734 F190588735 F190588808 F190588834 F190590835 F190590872 F190590891 F190593448 F190593449 F190593452 F190594403 F190594404 F190594420 F190594421 F190594431 F190594975 F190594976 F190595042 F190595043 F190595052 F190595242 F190595244 F190595245 F190595271 F190595915 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 8/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Table 2, List of Affected Serial Numbers F190595916 F190595917 F190598912 F190598913 G180387366 G180387366 G180387367 G180388034 G180388066 G180388988 G180389049 G180389507 G180389973 G180391808 G180391828 G180394646 G180394666 G180394667 G180394686 G180394687 G190599859 G190599940 G190600952 G190600972 G190604754 G190605223 G190605224 G190606763 G190608418 G190608752 G190608811 G190609714 G190609715 G190610692 G190610693 G190610731 G190611069 G190611070 G190611111 G190611954 G190613014 G190615153 G190615154 G190615155 H180395106 H180395126 H180395146 H180408665 H180408674 H180409087 H190619135 H190619136 H190619137 H190620042 H190620043 H190620388 H190620391 H190620793 H190620871 H190620872 H190620873 H190621202 H190621203 H190622245 H190622246 H190622247 H190622248 H190622249 H190622250 H190623084 H190623138 H190623195 H190623220 H190623502 H190623504 H190623505 H190623518 H190623519 H190624538 H190624539 H190624608 H190624612 H190624631 H190625403 H190625524 H190626070 H190626071 H190626137 H190626157 H190626158 H190626159 H190626173 H190626204 H190626862 H190626891 H190626892 H190626893 H190627234 H190627235 H190627236 H190629278 H190629931 H190630252 I170229858 I170230019 I170230019 I170230020 I180416026 I180416456 I180416466 I180416950 I180416966 I180416986 I180416987 I180416987 I190635292 I190635311 I190635331 I190636077 I190636078 I190636080 I190636081 I190637101 I190637102 I190637207 I190637231 I190637232 I190637467 I190637616 I190637617 I190637618 I190637619 I190637641 I190637651 I190640356 I190640397 I190640398 I190640399 I190640400 I190640401 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 9/10 2/21/2020 Campaign #4035: Fix for C100D2RE Generator Set Paralleling Control Wiring Issue Table 2, List of Affected Serial Numbers I190640591 I190640592 I190640593 I190640611 I190640612 I190640613 I190640631 I190641403 I190642492 I190644675 I190646057 I190646956 I190646993 I190646994 I190646995 I190646996 I190646997 I190647704 I190647706 I190648006 I190648007 I190648385 I190648402 I190651966 J180430767 J180430768 J180431068 J180437306 J180438418 J180438419 J180441866 J180441886 J180442399 J180442402 J180443311 K180460487 Document History Date Details 2019-12-17 Module Created 2020-1-24 Non-Product Problem Solving (PPS) 2020-2-13 Non-Product Problem Solving (PPS) Last Modified: 19-Feb-2020 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190225.html 10/10