TSB190037-031320
Service Bulletin Details
Public Details for: TSB190037-031320
This technical service bulletin describes the verification and resolution of incorrect wiring of rental generator sets external remote start connections with ats systems. Using a voltage and/or ground source from the ats connection and conn
- 9999 -
Models from 9999
9999 CUMMINS C |
External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2... Page 1 of 4 Technical Service Bulletin Technical Service Bulletin: Released Date: 13-Mar-2019 TSB190037 External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2RE, C150D2RE, C200D2RE, C275D2RE and Automatic Transfer Switch External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2RE, C150D2RE, C200D2RE, C275D2RE and Automatic Transfer Switch Warranty Statement The information in this document has no effect on present warranty coverage or repair practices, nor does it authorize TRP or Campaign actions. Contents Product Affected Rental Products: • • • • • C70D2RE C100D2RE C150D2RE C200D2RE C275D2RE Issue Incorrect wiring of rental generator sets External Remote Start connections with ATS systems. • Customers/Distributors are incorrectly wiring ATS systems to rental generator sets External Remote Start by using a voltage and/or Ground source from the ATS connection and connecting it to rental generator sets External Remote Start https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190037.html 3/18/2019 External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2... Page 2 of 4 connections (Dry Contacts Only). Doing this will cause equipment damage and failure. Verification/Confirmation The PowerCommand control outputs a 24Vdc signal to Terminal 1 of the external Remote Start Panel. Closing the contacts between Terminal 1 and Terminal 2 will complete the circuit and remotely start the generator set. Closing the contacts between Terminal 1 and Terminal 2 could be done by using a “Dry Contact” circuit with a remote start switch, transfer switch, or other similar devices. Applying any voltage and/or Ground to Terminal 1 or Terminal 2 will cause equipment damage and failure Resolution Removal of the Jumper at TB2-2 on the ATS Interconnection Terminal will convert the circuit into a “Dry Contact” state. Instructions for Interconnection wiring of ATS systems and Rental generator sets has been created to insure correct and proper wiring are being performed. Service Instructions How to properly connect the Remote Start System between Cummins’ ATS and Rental Products (Only use this layout for Rental and ATS systems) ATS Terminal Block Interconnection to Rental Generator Set PCC 1302 and PC 3.3 Control Board 1. Please refer to your current ATS Service Manuals - Interconnection Diagram. ATS Terminal Block Interconnection to Rental Generator Set External Remote Contacts 1. Ensure that NO JUMPER connections are between TB2-2 and TB2-1/TB2-3. Remove jumper if present. Failure to do so will cause equipment damage and failure. https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190037.html 3/18/2019 External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2... Page 3 of 4 Figure 1, ATS Interconnection Terminal 2. Route wire from TB2-2 and TB2-4 from the ATS Interconnection Terminals to the external Remote Start connection terminals found on the Rental generator set control box panel. https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190037.html 3/18/2019 External Remote Start Interconnection Wiring Issue between Rental C70D2RE, C100D2... Page 4 of 4 Figure 2, Wire Routing Document History Date 2019-3-7 Details Module Created Last Modified: 13-Mar-2019 https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2019/tsb190037.html 3/18/2019